Wago
Part No. 753-409

This digital impulse interface connects magnetostrictive position sensors equipped with a start/stop interface. After receiving a read pulse, these sensors deliver a time-delayed reply impulse. The time delay is proportional to the sensor distance. Each sensor may have up to four position transmitters (permanent magnets). Their position data can be accessed serially by the controller and are stored in the process image of the fieldbus coupler as a 24-bit value. The parameterization of the ultrasonic speed and the transmission points is done via the control byte. The parameters can be changed during operation. The transmission of the impulses is done with RS-422 differential drivers which guarantees trouble-free data transmission. Position sensors with the following features can be used: Start/stop interface with RS-422 differential signals, 24 V sensor supply, manufacturer: e.g., Balluff
Note | Pluggable connectors and coding fingers (753 Series) are not included. |
Number of inputs | 1 |
Signal type | Differential signal (RS-422) |
Encoder connection | Start/stop; Initialization; Uv; Ground; Shield connection via encoder housing |
Resolution | 1 µm |
Update time (update rate) | 2 |
Data width | 1 x 24-bit data 1 x 8-bit control/status |
Position sensor length | 4 |
Hysteresis (precision) | Depends on position sensor |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 45 |
Supply voltage (field) | 24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Isolation | 500 V system/field |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Connection technology: inputs / outputs | 8 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 9 … 10 mm / 0.35 … 0.39 inches |
Connection requirement (permissible cable length) | 500 |
Connection requirement (permissible cable type) | RS-422 |
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 69.8 mm / 2.748 inches |
Depth from upper-edge of DIN-rail | 62.6 mm / 2.465 inches |
Mounting type | DIN-35 rail |
Pluggable connector | Pluggable |
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 1.153 |
Weight | 42 |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2 |
EMC emission of interference | per EN 61000-6-4 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |