Skip to main content
IIDM Logo
753-635

Description

This digital impulse interface connects magnetostrictive position sensors equipped with a start/stop interface. After receiving a read pulse, these sensors deliver a time-delayed reply impulse. The time delay is proportional to the sensor distance. Each sensor may have up to four position transmitters (permanent magnets). Their position data can be accessed serially by the controller and are stored in the process image of the fieldbus coupler as a 24-bit value. The parameterization of the ultrasonic speed and the transmission points is done via the control byte. The parameters can be changed during operation. The transmission of the impulses is done with RS-422 differential drivers which guarantees trouble-free data transmission. Position sensors with the following features can be used: Start/stop interface with RS-422 differential signals, 24 V sensor supply, manufacturer: e.g., Balluff

Notes

Note

Pluggable connectors and coding fingers (753 Series) are not included.

Technical data

Number of inputs

1

Signal type

Differential signal (RS-422)

Encoder connection

Start/stop; Initialization; Uv; Ground; Shield connection via encoder housing

Resolution

1 µm

Update time (update rate)

2

Data width

1 x 24-bit data 1 x 8-bit control/status

Position sensor length

4

Hysteresis (precision)

Depends on position sensor

Supply voltage (system)

5 VDC; via data contacts

Current consumption (5 V system supply)

45

Supply voltage (field)

24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)

Isolation

500 V system/field

Number of incoming power jumper contacts

2

Number of outgoing power jumper contacts

2

Connection data

Connection technology: inputs / outputs

8 x CAGE CLAMP®

Connection type 1

Inputs/Outputs

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Strip length

9 … 10 mm / 0.35 … 0.39 inches

Connection requirement (permissible cable length)

500

Connection requirement (permissible cable type)

RS-422

Physical data

Width

12 mm / 0.472 inches

Height

100 mm / 3.937 inches

Depth

69.8 mm / 2.748 inches

Depth from upper-edge of DIN-rail

62.6 mm / 2.465 inches

Mechanical data

Mounting type

DIN-35 rail

Pluggable connector

Pluggable

Material data

Color

light gray

Housing material

Polycarbonate; polyamide 6.6

Fire load

1.153

Weight

42

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

0 … 2000 m / 0 … 6562 ft

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Vibration resistance

per IEC 60068-2-6

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61000-6-2

EMC emission of interference

per EN 61000-6-4

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Specifications

Connection data

Connectable Conductor MaterialsCopper
Connection Requirement (Permissible Cable Length)500
Connection Requirement (Permissible Cable Type)RS-422
Connection Technology: Inputs / Outputs8 x CAGE CLAMP®
Connection Type 1Inputs/Outputs
Fine-Stranded Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Solid Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Strip Length9 … 10 mm / 0.35 … 0.39 inches

Environmental requirements

Ambient Temperature (Operation)0 … +55 °C °C
EMC Emission Of Interferenceper EN 61000-6-4
EMC Immunity To Interferenceper EN 61000-6-2
Exposure To PollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Mounting Positionhorizontal (standing/lying); vertical
Operating Altitude0 … 2000 m / 0 … 6562 ft
Permissible Pollutant Concentration H2S At A Relative Humidity < 75%10
Permissible Pollutant Concentration SO 2 At A Relative Humidity < 75%25
Pollution Degree (5)2 per IEC 61131-2
Protection TypeIP20
Relative Humidity (Without Condensation)95
Shock Resistance15g per IEC 60068-2-27
Surrounding Air Temperature (Storage)-25 … +85 °C
Vibration Resistanceper IEC 60068-2-6

Material data

Colorlight gray
Conformity MarkingCE
Fire Load1.153
Housing MaterialPolycarbonate; polyamide 6.6
Weight42

Mechanical data

Mounting TypeDIN-35 rail
Pluggable ConnectorPluggable

Notes

NotePluggable connectors and coding fingers (753 Series) are not included.

Physical data

Depth69.8 mm / 2.748 inches mm
Depth From Upper-Edge Of DIN-Rail62.6 mm / 2.465 inches
Height100 mm / 3.937 inches mm
Width12 mm / 0.472 inches mm

Technical data

Current Consumption (5 V System Supply)45
Data Width1 x 24-bit data 1 x 8-bit control/status
Encoder ConnectionStart/stop; Initialization; Uv; Ground; Shield connection via encoder housing
Hysteresis (Precision)Depends on position sensor
Isolation500 V system/field
Number Of Incoming Power Jumper Contacts2
Number Of Inputs1
Number Of Outgoing Power Jumper Contacts2
Position Sensor Length4
Resolution1 µm
Signal TypeDifferential signal (RS-422)
Supply Voltage (Field)24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
Supply Voltage (System)5 VDC; via data contacts
Update Time (Update Rate)2

Similar products