Wago
Part No. 750-636
The 750-640 RTC Module provides the higher-level control system with the actual time. The time is buffered and continues to run in the event of a power failure. When an external receiver is connected, the clock can be set using the time signal from DCF77, WWVB, or MSF. By default, the module is set to receive DCF77 signals. The receiver can be supplied directly via the module. Connecting an external receiver to operate the RTC module is not absolutely necessary. With its 32 channels, the integrated time switch clock function makes it easier for the control unit to process time-triggered actions. The module also counts the power-on time of the 32 channels.
Device-specific | Accuracy (25 °C): < 1 minutes/month; Accuracy (10 … 40 °C): < 2 minutes/month; Accuracy (-25 … +85 °C): < 7 minutes/month; Drift: < 2 minutes/year |
Input filter | 10 ms |
Input current at specific input voltage | 5 mA at 24 V |
Input current at specific input voltage (2) | 1 mA bei 5 V |
Open-circuit voltage | 4 |
Output voltage | 5 … 24 VDC; Supply V ant, in |
Voltage range for signal (0) | −24 … +1 VDC |
Voltage range for signal (1) | 3 … 24 VDC |
Clock timer | 32 channels and switch points (32 x on/off) |
Buffer length | 6 |
Data width | 1 x 40-bit data (input/output) (5-byte user data) 1 x 8-bit control/status (optional) |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 20 |
Supply voltage (field) | 24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Current consumption, field supply (module with no external load) | 11 |
Isolation | 500 V system/field |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Connection technology: inputs / outputs | 8 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 69.8 mm / 2.748 inches |
Depth from upper-edge of DIN-rail | 62.6 mm / 2.465 inches |
Mounting type | DIN-35 rail |
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.951 |
Weight | 49.5 |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2 |
EMC emission of interference | per EN 61000-6-3 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |