Description

The 750-640 RTC Module provides the higher-level control system with the actual time. The time is buffered and continues to run in the event of a power failure. When an external receiver is connected, the clock can be set using the time signal from DCF77, WWVB, or MSF. By default, the module is set to receive DCF77 signals. The receiver can be supplied directly via the module. Connecting an external receiver to operate the RTC module is not absolutely necessary. With its 32 channels, the integrated time switch clock function makes it easier for the control unit to process time-triggered actions. The module also counts the power-on time of the 32 channels.

Technical data

Device-specific

Accuracy (25 °C): < 1 minutes/month; Accuracy (10 … 40 °C): < 2 minutes/month; Accuracy (-25 … +85 °C): < 7 minutes/month; Drift: < 2 minutes/year

Input filter

10 ms

Input current at specific input voltage

5 mA at 24 V

Input current at specific input voltage (2)

1 mA bei 5 V

Open-circuit voltage

4

Output voltage

5 … 24 VDC; Supply V ant, in

Voltage range for signal (0)

−24 … +1 VDC

Voltage range for signal (1)

3 … 24 VDC

Clock timer

32 channels and switch points (32 x on/off)

Buffer length

6

Data width

1 x 40-bit data (input/output) (5-byte user data) 1 x 8-bit control/status (optional)

Supply voltage (system)

5 VDC; via data contacts

Current consumption (5 V system supply)

20

Supply voltage (field)

24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)

Current consumption, field supply (module with no external load)

11

Isolation

500 V system/field

Number of incoming power jumper contacts

2

Number of outgoing power jumper contacts

2

Connection data

Connection technology: inputs / outputs

8 x CAGE CLAMP®

Connection type 1

Inputs/Outputs

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Physical data

Width

12 mm / 0.472 inches

Height

100 mm / 3.937 inches

Depth

69.8 mm / 2.748 inches

Depth from upper-edge of DIN-rail

62.6 mm / 2.465 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

light gray

Housing material

Polycarbonate; polyamide 6.6

Fire load

0.951

Weight

49.5

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

0 … 2000 m / 0 … 6562 ft

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Vibration resistance

per IEC 60068-2-6

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61000-6-2

EMC emission of interference

per EN 61000-6-3

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Specifications

Connection data

Connection Technology: Inputs / Outputs8 x CAGE CLAMP®
Connection Type 1Inputs/Outputs
Fine-Stranded Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Solid Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Strip Length8 … 9 mm / 0.31 … 0.35 inches

Environmental requirements

Ambient Temperature (Operation)0 … +55 °C °C
EMC Emission Of Interferenceper EN 61000-6-3
EMC Immunity To Interferenceper EN 61000-6-2
Exposure To PollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Mounting Positionhorizontal (standing/lying); vertical
Operating Altitude0 … 2000 m / 0 … 6562 ft
Permissible Pollutant Concentration H2S At A Relative Humidity < 75%10
Permissible Pollutant Concentration SO 2 At A Relative Humidity < 75%25
Pollution Degree (5)2 per IEC 61131-2
Protection TypeIP20
Relative Humidity (Without Condensation)95
Shock Resistance15g per IEC 60068-2-27
Surrounding Air Temperature (Storage)-25 … +85 °C
Vibration Resistanceper IEC 60068-2-6

Material data

Colorlight gray
Conformity MarkingCE
Fire Load0.951
Housing MaterialPolycarbonate; polyamide 6.6
Weight49.5

Mechanical data

Mounting TypeDIN-35 rail

Physical data

Depth69.8 mm / 2.748 inches mm
Depth From Upper-Edge Of DIN-Rail62.6 mm / 2.465 inches
Height100 mm / 3.937 inches mm
Width12 mm / 0.472 inches mm

Technical data

Buffer Length6
Clock Timer32 channels and switch points (32 x on/off)
Current Consumption (5 V System Supply)20
Current Consumption, Field Supply (Module With No External Load)11
Data Width1 x 40-bit data (input/output) (5-byte user data) 1 x 8-bit control/status (optional)
Device-SpecificAccuracy (25 °C): < 1 minutes/month; Accuracy (10 … 40 °C): < 2 minutes/month; Accuracy (-25 … +85 °C): < 7 minutes/month; Drift: < 2 minutes/year
Input Current At Specific Input Voltage5 mA at 24 V
Input Current At Specific Input Voltage (2)1 mA bei 5 V
Input Filter10 ms
Isolation500 V system/field
Number Of Incoming Power Jumper Contacts2
Number Of Outgoing Power Jumper Contacts2
Open-Circuit Voltage4
Output Voltage5 … 24 VDC; Supply V ant, in
Supply Voltage (Field)24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
Supply Voltage (System)5 VDC; via data contacts
Voltage Range For Signal (0)−24 … +1 VDC
Voltage Range For Signal (1)3 … 24 VDC

Similar products