Wago
Part No. 750-332

This controller can accommodate up to two KNX logic devices at the same time. 1. In conjunction with the WAGO I/O System, the KNX IP Controller is used as a user-programmable application controller within KNX IP networks. The controller supports all digital, analog and specialty modules found within the 750/753 Series. The IEC 61131-3 programmable controller is capable of 10/100 Mbit/s data rates. KNX objects of any type (EIS/DPT) can be created using the programming tool. Libraries including pre-made function blocks are readily available on the WAGO Website for programming. The controller supports a maximum of 253 communication objects, as well as 254 group addresses and associations. 2. Combined with the KNX/EIB/TP1 Module, the 750‐889 KNX IP Controller operates as a router on an IP backbone (ETHERNET). No IEC application is required for router functionality. Both devices are commissioned and configured via ETS software using the WAGO product database. The software includes a plug‐in that automatically installs and opens for configuration. The KNX IP Controller features an integrated 2‐port 10/100 Mbit/s switch, allowing a line structure to be easily created without additional network components. The maximum number of controllers that can be wired in series is 20. An internal server is available for Web-based applications. The controller provides 1024 KB program memory, 1024 KB data memory and 32 KB retain memory. It is capable of multitasking, has a battery-backed, real-time clock and is based on a 32-bit CPU. The controller offers many different application protocols for control tasks (MODBUS, KNXnet/IP) or for system management and diagnostics (HTTP, BootP, DHCP, DNS, AutoIP, SNTP, FTP, SNMP and SMTP). The number of KNX/EIB/TP1 Modules (750‐646) supported by the KNX IP Controller does not depend on the application.
Note | The WAGO ETS3/4 plug-in is a component of the WAGO-ETS3 product databank and can be downloaded for free at www.wago.com. |
Communication | KNX IP Modbus (TCP, UDP) ETHERNET |
ETHERNET protocols | HTTP BootP DHCP DNS AutoIP SNTP FTP SNMP V3 SMTP |
Visualization | Web-Visu |
CPU | 32 bits |
Programming languages per IEC 61131-3 | Instruction List (IL) Ladder Diagram (LD) Function Block Diagram (FBD), Continuous Function Chart (CFC) Structured Text (ST) Sequential Function Chart (SFC) |
Programming environment | WAGO-I/O-PRO V2.3 (based on CODESYS V2.3) |
Configuration options | WAGO-I/O-CHECK Web-Based Management |
Device specification | KNX/TP1 bus specification: 1.0 |
Network length (max.) | ≤ 2000 m; max. 20 controllers in series |
Baud rate (communication/fieldbus 1) | 10/100 Mbit/s |
Baud rate | 10/100 Mbit/s |
Bus segment length (max.) | 100 m |
Transmission medium (communication/fieldbus) | S-UTP; 100 Ω; Cat. 5 |
Program memory | 1024 KB |
Data memory | 1024 KB |
Non-volatile software memory | 32 |
Memory for fieldbus input variables (max.) | 512 |
Memory for fieldbus output variables (max.) | 512 |
Type of memory card | SD card |
Memory card slot | Push-push mechanism; Cover lid (sealable) |
Number of modules per node (max.) | 250 |
Number of modules without a bus extension (max.) | 64 |
Input and output process image (fieldbus) max. | 1020 Worte/1020 Worte |
Device-specific | Number of group addresses: 254; Number of communication objects: 253 |
Indicators | LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS/PRG IP, NS/PRG RT) red/green: IP device programming mode, router; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply |
Supply voltage (system) | 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection) |
Input current (typ.) at nominal load (24 V) | 500 |
Power supply efficiency (typ.) at nominal load (24 V) | 90 |
Current consumption (5 V system supply) | 450 |
Total current (system supply) | 1,700 |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts |
Current carrying capacity (power jumper contacts) | 10 |
Number of outgoing power jumper contacts | 3 |
Isolation | 500 V system/field |
KNX certified | IP Controller: 61/8316/08; IP Router: 61/8317/08 |
Connection technology: communication/fieldbus | KNX IP: 2 x RJ-45; Modbus TCP/UDP: 2 x RJ-45 |
Connection technology: system supply | 2 x CAGE CLAMP® |
Connection technology: field supply | 6 x CAGE CLAMP® |
Connection type 1 | System/field supply |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Connection technology: device configuration | 1 x Male connector; 4-pole |
Width | 61.5 mm / 2.421 inches |
Height | 100 mm / 3.937 inches |
Depth | 71.9 mm / 2.831 inches |
Depth from upper-edge of DIN-rail | 64.7 mm / 2.547 inches |
Weight | 192 |
Color | gray |
Housing material | Polycarbonate; polyamide 6.6 |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.) |
Relative humidity (without condensation) | 95 |
Mounting position | any |
Mounting type | DIN-35 rail |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2 |
EMC emission of interference | per EN 61000-6-3 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Fire load | 2.802 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |