Wago
Part No. 750-337

This fieldbus coupler connects the WAGO I/O System as a slave to the DeviceNet fieldbus. The fieldbus coupler detects all connected I/O modules and creates a local process image. Analog and specialty module data is sent via words and/or bytes; digital data is sent bit by bit. The process image can be transferred via the DeviceNet fieldbus to the memory of the control system. The local process image is divided into two data zones containing the data received and the data to be sent. The process data can be sent via the DeviceNetTM to a control system for further processing. The process output data is sent via DeviceNetTM. The data of the analog modules is stored in the process image that is created automatically according to the order in which the modules are connected to the coupler. The bits of the digital modules are sent byte by byte and added to the analog data. If the amount of digital I/O information exceeds eight bits, the coupler automatically starts with a new byte.
Note | Note: Configuration files required (EDS)! |
Communication | DeviceNet |
Number of fieldbus nodes on master (max.) | 64 |
Number of I/O points | 6,000 |
Baud rate | 500 kBd (125 kBd, 250 kBd, 500 kBd) |
Bus segment length (max.) | 500 m |
Transmission medium | Shielded Cu cable; Remote bus cable: 2 x 0.82 mm² + 2 x 1.7 mm²; Drop cable: 2 x 0.2 mm² + 2 x 0.32 mm² |
Number of modules per node (max.) | 64 |
DeviceNet features | Polled I/O message connection Strobed I/O message connection Change of state Cyclic message connection Group 2 only Slave |
Input and output process image (fieldbus) max. | 512 bytes/512 bytes |
Supply voltage (system) | 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection) |
Current consumption (5 V system supply) | 350 |
Total current (system supply) | 1,650 |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts |
Input current via DeviceNet interface at 11 V | 120 |
Input current (typ.) at nominal load (24 V) | 500 |
Power supply efficiency (typ.) at nominal load (24 V) | 87 |
Isolation | 500 V system/field |
Number of outgoing power jumper contacts | 3 |
Current carrying capacity (power jumper contacts) | 10 |
Certification | ODVA |
Connection technology: communication/fieldbus | DeviceNet: 1 x Male connector; 5-pole |
Connection technology: field supply | 6 x CAGE CLAMP® |
Connection technology: system supply | 2 x CAGE CLAMP® |
Connection technology: device configuration | 1 x Male connector; 4-pole |
Connection type 1 | System/field supply |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Width | 50.5 mm / 1.988 inches |
Height | 100 mm / 3.937 inches |
Depth | 71.1 mm / 2.799 inches |
Depth from upper-edge of DIN-rail | 63.9 mm / 2.516 inches |
Mounting type | DIN-35 rail |
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 3.302 |
Weight | 200 |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-4, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |