Wago
Part No. 750-564

Increasingly complex products, manufacturing flexibility and high demands on quality assurance require intelligent, configurable and programmable sensors. To fulfill these demands, IO-Link streamlines the varying interfaces required to connect to a control system and tooling. A 3-wire connection can communicate process data (as single bits, bytes and data blocks for input and output data). It also communicates acyclic data (for identification, configuration, parameterization and diagnostics) with up to 230.4 kBaud to both sensors and actuators. The functions and performance data are defined in device description files for master and devices; these are easy to customize via WAGO-I/O-CHECK. If a device must be replaced, the configuration and parameterization can be automatically restored without maintenance personnel. Project design, installation and operation are simplified! Four different IO-Link devices or standard digital sensors/actuators can simultaneously connect to the WAGO 750-657 IO-Link Master. At just 12 mm (0.47 inch) wide, the module has three connections for each of the four channels.
Topology | Number of IO-Link ports: 4 |
Sensor connection | 4 x (3-wire) |
Actuator connection | 4 x (3-wire) |
Transmission modes | 4.8 kBaud (COM 1), 38.4 kBaud (COM 2), 230.4 kBaud (COM 3) |
Data width | 4–24 bytes, configurable |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 40 |
Supply voltage (field) | 24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Current consumption, field supply (module with no external load) | 50 |
Isolation | 500 V system/field |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Connection technology: inputs / outputs | 16 x Push-in CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 1.5 mm² / 28 … 16 AWG |
Fine-stranded conductor | 0.25 … 1.5 mm² / 22 … 16 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Connection requirement (permissible cable length) | 20 |
Conductor type (1) | f-st |
Conductor type (2) | s |
Conductor type 1 | fine-stranded |
Conductor type 2 | solid |
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 69 mm / 2.717 inches |
Depth from upper-edge of DIN-rail | 61.8 mm / 2.433 inches |
Mounting type | DIN-35 rail |
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.824 |
Weight | 49.6 |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, EN 61131-2 |
EMC emission of interference | per EN 61000-6-4, EN 61131-2 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |