Skip to main content
IIDM Logo
750-657

Description

Increasingly complex products, manufacturing flexibility and high demands on quality assurance require intelligent, configurable and programmable sensors. To fulfill these demands, IO-Link streamlines the varying interfaces required to connect to a control system and tooling. A 3-wire connection can communicate process data (as single bits, bytes and data blocks for input and output data). It also communicates acyclic data (for identification, configuration, parameterization and diagnostics) with up to 230.4 kBaud to both sensors and actuators. The functions and performance data are defined in device description files for master and devices; these are easy to customize via WAGO-I/O-CHECK. If a device must be replaced, the configuration and parameterization can be automatically restored without maintenance personnel. Project design, installation and operation are simplified! Four different IO-Link devices or standard digital sensors/actuators can simultaneously connect to the WAGO 750-657 IO-Link Master. At just 12 mm (0.47 inch) wide, the module has three connections for each of the four channels.

Technical data

Topology

Number of IO-Link ports: 4

Sensor connection

4 x (3-wire)

Actuator connection

4 x (3-wire)

Transmission modes

4.8 kBaud (COM 1), 38.4 kBaud (COM 2), 230.4 kBaud (COM 3)

Data width

4–24 bytes, configurable

Supply voltage (system)

5 VDC; via data contacts

Current consumption (5 V system supply)

40

Supply voltage (field)

24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)

Current consumption, field supply (module with no external load)

50

Isolation

500 V system/field

Number of incoming power jumper contacts

2

Number of outgoing power jumper contacts

2

Connection data

Connection technology: inputs / outputs

16 x Push-in CAGE CLAMP®

Connection type 1

Inputs/Outputs

Solid conductor

0.08 … 1.5 mm² / 28 … 16 AWG

Fine-stranded conductor

0.25 … 1.5 mm² / 22 … 16 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Connection requirement (permissible cable length)

20

Conductor type (1)

f-st

Conductor type (2)

s

Conductor type 1

fine-stranded

Conductor type 2

solid

Physical data

Width

12 mm / 0.472 inches

Height

100 mm / 3.937 inches

Depth

69 mm / 2.717 inches

Depth from upper-edge of DIN-rail

61.8 mm / 2.433 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

light gray

Housing material

Polycarbonate; polyamide 6.6

Fire load

0.824

Weight

49.6

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

0 … 2000 m / 0 … 6562 ft

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Vibration resistance

per IEC 60068-2-6

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61000-6-2, EN 61131-2

EMC emission of interference

per EN 61000-6-4, EN 61131-2

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Specifications

Connection data

Conductor Type (1)f-st | fine-stranded
Conductor Type (2)s | solid
Connection Requirement (Permissible Cable Length)20
Connection Technology: Inputs / Outputs16 x Push-in CAGE CLAMP®
Connection Type 1Inputs/Outputs
Fine-Stranded Conductor0.25 … 1.5 mm² / 22 … 16 AWG
Solid Conductor0.08 … 1.5 mm² / 28 … 16 AWG
Strip Length8 … 9 mm / 0.31 … 0.35 inches

Environmental requirements

Ambient Temperature (Operation)0 … +55 °C °C
EMC Emission Of Interferenceper EN 61000-6-4, EN 61131-2
EMC Immunity To Interferenceper EN 61000-6-2, EN 61131-2
Exposure To PollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Mounting Positionhorizontal (standing/lying); vertical
Operating Altitude0 … 2000 m / 0 … 6562 ft
Permissible Pollutant Concentration H2S At A Relative Humidity < 75%10
Permissible Pollutant Concentration SO 2 At A Relative Humidity < 75%25
Pollution Degree (5)2 per IEC 61131-2
Protection TypeIP20
Relative Humidity (Without Condensation)95
Shock Resistance15g per IEC 60068-2-27
Surrounding Air Temperature (Storage)-25 … +85 °C
Vibration Resistanceper IEC 60068-2-6

Material data

Colorlight gray
Conformity MarkingCE
Fire Load0.824
Housing MaterialPolycarbonate; polyamide 6.6
Weight49.6

Mechanical data

Mounting TypeDIN-35 rail

Physical data

Depth69 mm / 2.717 inches mm
Depth From Upper-Edge Of DIN-Rail61.8 mm / 2.433 inches
Height100 mm / 3.937 inches mm
Width12 mm / 0.472 inches mm

Technical data

Actuator Connection4 x (3-wire)
Current Consumption (5 V System Supply)40
Current Consumption, Field Supply (Module With No External Load)50
Data Width4–24 bytes, configurable
Isolation500 V system/field
Number Of Incoming Power Jumper Contacts2
Number Of Outgoing Power Jumper Contacts2
Sensor Connection4 x (3-wire)
Supply Voltage (Field)24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
Supply Voltage (System)5 VDC; via data contacts
TopologyNumber of IO-Link ports: 4
Transmission Modes4.8 kBaud (COM 1), 38.4 kBaud (COM 2), 230.4 kBaud (COM 3)

Similar products

More from Wago