Skip to main content
IIDM Logo
750-643

Description

The 750-643 Module acts as a master for the MP bus (Multi-Point bus from Belimo/Switzerland) and allows the bus to be integrated into a higher level bus network such as ETHERNET or LONWORKS®. The MP-Bus controls HVAC actuators for dampers, regulator valves or VAV air volume controls. An additional product series for MP-Bus connection is the window ventilation system (FLS) from Belimo (MP-Bus connection for Belimo actuators, see Belimo documentation). Devices that are equipped with an MP-Bus connection (e.g., Belimo MFT actuator series) can communicate with a higher-level control system via bus cable. The actuators have connections for sensors (temperature, humidity, on/off switch) that are also accessible via MP-Bus. An MP-Bus Master can manage up to eight slaves (actuators) and eight sensors (one sensor can be connected to each slave) via a common bus line, which considerably reduces actuator and sensor wiring (for MP-bus cable lengths, see Belimo documentation). *Documentation available in German and English. A Belimo parameterization unit (hand-held control unit, or Belimo PC tool) can be connected to the module to configure the Belimo actuators. The enable handheld contact can be used for this. The module deactivates its MP-bus communication when the external parameterization unit is connected to this contact (or simply to the +24 V power supply).

Technical data

Device specification

MP-Bus Specification: PP/MP Specification V1.21 from Belimo (Valid since 1.10.2002)

Topology

Number of participants: 8 slaves (max.)

Current consumption (typ.)

25 mA (MP-Bus)

Data width

1-byte C/S, 7-byte data

Power supply

MP-Bus: 24 VDC, via power jumper contacts

Supply voltage (system)

5 VDC; via data contacts

Current consumption (5 V system supply)

15

Supply voltage (field)

24 VDC; via power jumper contacts (power supply via blade contact; transmission via spring contact)

Isolation

500 V (rms) MP-Bus/system

Number of incoming power jumper contacts

2

Number of outgoing power jumper contacts

2

Connection data

Connection technology: inputs / outputs

8 x CAGE CLAMP®

Connection type 1

Inputs/Outputs

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Physical data

Width

12 mm / 0.472 inches

Height

100 mm / 3.937 inches

Depth

69.8 mm / 2.748 inches

Depth from upper-edge of DIN-rail

62.6 mm / 2.465 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

light gray

Housing material

Polycarbonate; polyamide 6.6

Fire load

1.024

Weight

50.5

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

0 … 2000 m / 0 … 6562 ft

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Vibration resistance

per IEC 60068-2-6

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61000-6-2

EMC emission of interference

per EN 61000-6-3

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Specifications

Connection data

Connectable Conductor MaterialsCopper
Connection Technology: Inputs / Outputs8 x CAGE CLAMP®
Connection Type 1Inputs/Outputs
Fine-Stranded Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Solid Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Strip Length8 … 9 mm / 0.31 … 0.35 inches

Environmental requirements

Ambient Temperature (Operation)0 … +55 °C °C
EMC Emission Of Interferenceper EN 61000-6-3
EMC Immunity To Interferenceper EN 61000-6-2
Exposure To PollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Mounting Positionhorizontal (standing/lying); vertical
Operating Altitude0 … 2000 m / 0 … 6562 ft
Permissible Pollutant Concentration H2S At A Relative Humidity < 75%10
Permissible Pollutant Concentration SO 2 At A Relative Humidity < 75%25
Pollution Degree (5)2 per IEC 61131-2
Protection TypeIP20
Relative Humidity (Without Condensation)95
Shock Resistance15g per IEC 60068-2-27
Surrounding Air Temperature (Storage)-25 … +85 °C
Vibration Resistanceper IEC 60068-2-6

Material data

Colorlight gray
Conformity MarkingCE
Fire Load1.024
Housing MaterialPolycarbonate; polyamide 6.6
Weight50.5

Mechanical data

Mounting TypeDIN-35 rail

Physical data

Depth69.8 mm / 2.748 inches mm
Depth From Upper-Edge Of DIN-Rail62.6 mm / 2.465 inches
Height100 mm / 3.937 inches mm
Width12 mm / 0.472 inches mm

Technical data

Current Consumption (5 V System Supply)15
Current Consumption (Typ.)25 mA (MP-Bus)
Data Width1-byte C/S, 7-byte data
Device SpecificationMP-Bus Specification: PP/MP Specification V1.21 from Belimo (Valid since 1.10.2002)
Isolation500 V (rms) MP-Bus/system
Number Of Incoming Power Jumper Contacts2
Number Of Outgoing Power Jumper Contacts2
Power SupplyMP-Bus: 24 VDC, via power jumper contacts
Supply Voltage (Field)24 VDC; via power jumper contacts (power supply via blade contact; transmission via spring contact)
Supply Voltage (System)5 VDC; via data contacts
TopologyNumber of participants: 8 slaves (max.)

Similar products