Bardac
Part No. p2 series































| Frame Size | 1 | 1 | 2 | 2 | 3 | 3 | 4 | 4 | 5 |
| Protection | IP20 | NEMA 4X (IP66) | IP20 | NEMA 4X (IP66) | IP20 | NEMA 4X (IP66) | IP20 | NEMA 4X (IP66) | IP20 |
| Height (ins) | 6.8” | 9.2" | 8.7” | 10.1" | 10.3” | 12.2" | 16.6" | 14.2" | 19.13" |
| Height (mm) | 173 | 232 | 221 | 257 | 261 | 310 | 420 | 360 | 486 |
| Width (ins) | 3.3" | 6.4" | 4.4" | 7.4" | 5.2" | 8.3” | 6.8" | 9.5” | 8.74" |
| Width (mm) | 83 | 161 | 110 | 188 | 131 | 211 | 171 | 240 | 222 |
| Depth (ins) | 4.9" | 7.1" | 5.9” | 7.4” | 6.9” | 9.9” | 8.4” | 10.8” | 8.9” |
| Depth (mm) | 123 | 179 | 150 | 188 | 175 | 252 | 212 | 275 | 226 |
| Weight (lbs) | 2.2 | 6.8 | 3.75 | 9 | 7 | 16.7 | 20.0 | 20.9 | 37.26 |
| Weight (kg) | 1.0 | 3.1 | 1.7 | 4.1 | 3.2 | 7.6 | 9.1 | 9.5 | 16.9 |
Supply Voltage | 100 – 132 volts max, single phase (0.5 – 1.5HP) | 180 – 264 volts max, 1-phase (0.5 – 3HP) | 180 – 264 volts max, 3-phase (0.5 – 5HP) | 342 – 528 volts max, 3-phase (1 – 30HP) |
Supply Frequency | 48 – 62 Hz |
Power Output | 230V, 0.5 to 15HP | 460V, 0.5 to 30HP |
Output Frequency | 0 to 500Hz | (Please call for special builds up to 2000Hz) |
Temperature | IP20, operating, -10 to 50°C max, storage, -40 to 60°C |
Altitude | 0-2000M, derate 1% per 100M above 1000M |
Humidity | Up to 95%, non condensing |
Ingress Protection | Basic IP20, Optional IP66 (NEMA 4X outdoor rated) |
Mode | Voltage vector |
PWM frequency | 4 to 32KHz (effective) |
V/Hz ratio | Linear |
Boost | Yes |
Stop modes | Coast / ramp / DC brake |
Skip frequency | One point, adjustable frequency band |
Setpoint reference | 0-10VDC, 4-20mA, 20-4mA, 0-20mA, Keypad, Modbus |
Preset speeds | 8 |
PI control | Direct & analog input trim |
Spin start | Starts safely into rotating motor |
Accel/Decel | 0 – 600 seconds + Ramp stop decel 0 – 600 seconds |
Input 1, Input 2 | Programmable digital input |
Input 3, Input 4 | Configurable analog or digital input |
Output 1 | Configurable analog or digital output |
Output 2 | Normally open relay contact 30VDC 5A, 250VAC 6A |
Drive trip | Over/under volts, over current, external trip |
Motor | Overload, over temperature, short circuit, ground fault |
Trip memory | Last 4 trips stored |