Wago
Part No. 752-9800/8000-001

In conjunction with the WAGO I/O System, the ETHERNET Controller serves ETHERNET networks requiring fast and safe media redundancy. The controller supports all digital, analog and specialty modules found within the 750/753 Series, and is suitable for data rates of 10/100 Mbit/s. Media redundancy is achieved by operating the controller in two separate networks – which is accessible via two different IP addresses (including two MAC IDs). Cross communication between separate channels is not possible. The two separate ETHERNET interfaces allow redundant connection of two transmission paths (no hub or switch required). Both interfaces support autonegotiation and Auto-MDI(X). The DIP switch configures the last byte of both default IP addresses and may be used for IP address assignment (DHCP, BootP). The media redundancy controller is designed for fieldbus communication via MODBUS in ETHERNET networks. It also supports a wide variety of standard ETHERNET protocols (HTTP, BootP, DHCP, DNS, FTP). An integrated Webserver provides user configuration options, while displaying the controllers status information. The device is programmable in accordance with IEC 61131-3, is multitasking-capable and features a battery-backed RTC.
Communication | EtherNet/IP Modbus (TCP, UDP) ETHERNET |
ETHERNET protocols | HTTP BootP DHCP DNS SNTP FTP SNMP |
Redundancy function | via two logically separated ETHERNET interfaces |
Visualization | Web-Visu Web Visu |
CPU | 32 bits |
Programming languages per IEC 61131-3 | Instruction List (IL) Ladder Diagram (LD) Function Block Diagram (FBD), Continuous Function Chart (CFC) Structured Text (ST) Sequential Function Chart (SFC) |
Programming environment | WAGO-I/O-PRO V2.3 (based on CODESYS V2.3) |
Configuration options | WAGO-I/O-CHECK Web-Based Management |
Baud rate (communication/fieldbus 1) | 10/100 Mbit/s |
Baud rate | 10/100 Mbit/s |
Transmission medium (communication/fieldbus) | Twisted Pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length |
Transmission performance | Class D per EN 50173 |
Program memory | 1024 KB |
Data memory | 512 KB |
Non-volatile software memory | 32 |
Number of modules per node (max.) | 250 |
Number of modules without a bus extension (max.) | 64 |
Input and output process image (fieldbus) max. | 1020 Worte/1020 Worte |
Indicators | LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS, NS) red/green: Status of node, network; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply |
Supply voltage (system) | 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection) |
Input current (typ.) at nominal load (24 V) | 500 |
Power supply efficiency (typ.) at nominal load (24 V) | 90 |
Current consumption (5 V system supply) | 450 |
Total current (system supply) | 1,700 |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts |
Current carrying capacity (power jumper contacts) | 10 |
Number of outgoing power jumper contacts | 3 |
Isolation | 500 V system/field |
Connection technology: communication/fieldbus | EtherNet/IPTM: 2 x RJ-45; Modbus TCP/UDP: 2 x RJ-45 |
Connection technology: system supply | 2 x CAGE CLAMP® |
Connection technology: field supply | 6 x CAGE CLAMP® |
Connection type 1 | System/field supply |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Connection technology: device configuration | 1 x Male connector; 4-pole |
Width | 61.5 mm / 2.421 inches |
Height | 100 mm / 3.937 inches |
Depth | 71.9 mm / 2.831 inches |
Depth from upper-edge of DIN-rail | 64.7 mm / 2.547 inches |
Weight | 159.2 |
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.) |
Relative humidity (without condensation) | 95 |
Mounting position | any |
Mounting type | DIN-35 rail |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-3, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Fire load | 3.533 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |