Skip to main content
IIDM Logo
750-833

Description

The PROFIBUS DP/V1 Controller combines control functionality, I/O interface and fieldbus in one device. Application programming is IEC 61131-3 compliant. The programmer can access all fieldbus and I/O data. Features and applications: Decentralized control to optimize support for a PLC or PC Devide complex applications into individually testable units Programmable fault response in the event of fieldbus failure Signal pre-processing to reduce fieldbus transmissions Directly control peripheral equipment for faster system response times Stand-alone, compact controller

Notes

Note

Note: Configuration files required (GSD)!

The GSD files can be downloaded for free at www.wago.com.

Technical data

Communication

PROFIBUS

Visualization

none

CPU

16 bits

Programming languages per IEC 61131-3

Instruction List (IL)

Ladder Diagram (LD)

Function Block Diagram (FBD), Continuous Function Chart (CFC)

Structured Text (ST)

Sequential Function Chart (SFC)

Programming environment

WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)

Configuration options

GSD device description file

WAGO-I/O-CHECK

Cycle time

< 3 ms for 1000 bit instructions/ 256 digital I/O

Baud rate

9.6 kBd … 12 MBd

Bus segment length (max.)

1200 m

Transmission medium (communication/fieldbus)

Cu cable per EN 50170

Transmission time

typ. 1 ms (10 controllers; each 32 digital I/O and 12 Mbaud) max. 3.3 ms

Number of fieldbus nodes on master (max.)

96

Number of I/O points

6,000

Program memory

128 KB

Data memory

64 KB

Non-volatile software memory

8

Memory for fieldbus input variables (max.)

244

Memory for fieldbus output variables (max.)

244

Number of modules per node (max.)

63

Input and output process image (fieldbus) max.

244 bytes/244 bytes

Indicators

LED (RUN) green: Fieldbus initialization, LED (BF, DIA, BUS) red: communication error, external diagnostics, configuration; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply

Supply voltage (system)

24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)

Input current (typ.) at nominal load (24 V)

500

Power supply efficiency (typ.) at nominal load (24 V)

87

Current consumption (5 V system supply)

200

Total current (system supply)

1,800

Supply voltage (field)

24 VDC (-25 … +30 %); via power jumper contacts

Current carrying capacity (power jumper contacts)

10

Number of outgoing power jumper contacts

3

Isolation

500 V system/field

Standard

EN 50170

Connection data

Connection technology: communication/fieldbus

PROFIBUS: 1 x D-Sub 9 socket

Connection technology: system supply

2 x CAGE CLAMP®

Connection technology: field supply

6 x CAGE CLAMP®

Connection type 1

System/field supply

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Connection technology: device configuration

1 x Male connector; 4-pole

Physical data

Width

50.5 mm / 1.988 inches

Height

100 mm / 3.937 inches

Depth

71.1 mm / 2.799 inches

Depth from upper-edge of DIN-rail

63.9 mm / 2.516 inches

Mechanical data

Weight

186.9

Color

light gray

Housing material

Polycarbonate; polyamide 6.6

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)

Relative humidity (without condensation)

95

Mounting position

any

Mounting type

DIN-35 rail

Vibration resistance

4g per IEC 60068-2-6

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61000-6-2, marine applications

EMC emission of interference

per EN 61000-6-4, marine applications

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Fire load

2.988

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Specifications

Connection data

Connectable Conductor MaterialsCopper
Connection Technology: Communication/FieldbusPROFIBUS: 1 x D-Sub 9 socket
Connection Technology: Device Configuration1 x Male connector; 4-pole
Connection Technology: Field Supply6 x CAGE CLAMP®
Connection Technology: System Supply2 x CAGE CLAMP®
Connection Type 1System/field supply
Fine-Stranded Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Solid Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Strip Length8 … 9 mm / 0.31 … 0.35 inches

Environmental requirements

Ambient Temperature (Operation)0 … +55 °C °C
EMC Emission Of Interferenceper EN 61000-6-4, marine applications
EMC Immunity To Interferenceper EN 61000-6-2, marine applications
Exposure To PollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Fire Load2.988
Mounting Positionany
Mounting TypeDIN-35 rail
Operating Altitudewithout temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
Permissible Pollutant Concentration H2S At A Relative Humidity < 75%10
Permissible Pollutant Concentration SO 2 At A Relative Humidity < 75%25
Pollution Degree (5)2 per IEC 61131-2
Protection TypeIP20
Relative Humidity (Without Condensation)95
Shock Resistance15g per IEC 60068-2-27
Surrounding Air Temperature (Storage)-25 … +85 °C
Vibration Resistance4g per IEC 60068-2-6

Mechanical data

Colorlight gray
Conformity MarkingCE
Housing MaterialPolycarbonate; polyamide 6.6
Weight186.9

Notes

NoteNote: Configuration files required (GSD)!The GSD files can be downloaded for free at www.wago.com.

Physical data

Depth71.1 mm / 2.799 inches mm
Depth From Upper-Edge Of DIN-Rail63.9 mm / 2.516 inches
Height100 mm / 3.937 inches mm
Width50.5 mm / 1.988 inches mm

Technical data

Baud Rate9.6 kBd … 12 MBd
Bus Segment Length (Max.)1200 m
CommunicationPROFIBUS
Configuration OptionsGSD device description file | WAGO-I/O-CHECK
CPU16 bits
Current Carrying Capacity (Power Jumper Contacts)10
Current Consumption (5 V System Supply)200
Cycle Time< 3 ms for 1000 bit instructions/ 256 digital I/O
Data Memory64 KB
IndicatorsLED (RUN) green: Fieldbus initialization, LED (BF, DIA, BUS) red: communication error, external diagnostics, configuration; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply
Input And Output Process Image (Fieldbus) Max.244 bytes/244 bytes
Input Current (Typ.) At Nominal Load (24 V)500
Isolation500 V system/field
Memory For Fieldbus Input Variables (Max.)244
Memory For Fieldbus Output Variables (Max.)244
Non-Volatile Software Memory8
Number Of Fieldbus Nodes On Master (Max.)96
Number Of I/O Points6,000
Number Of Modules Per Node (Max.)63
Number Of Outgoing Power Jumper Contacts3
Power Supply Efficiency (Typ.) At Nominal Load (24 V)87
Program Memory128 KB
Programming EnvironmentWAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
Programming Languages Per IEC 61131-3Instruction List (IL) | Ladder Diagram (LD) | Function Block Diagram (FBD), Continuous Function Chart (CFC) | Structured Text (ST) | Sequential Function Chart (SFC)
StandardEN 50170
Supply Voltage (Field)24 VDC (-25 … +30 %); via power jumper contacts
Supply Voltage (System)24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
Total Current (System Supply)1,800
Transmission Medium (Communication/Fieldbus)Cu cable per EN 50170
Transmission Timetyp. 1 ms (10 controllers; each 32 digital I/O and 12 Mbaud) max. 3.3 ms
Visualizationnone