Wago
Part No. 750-469/000-012

The data exchange module allows the exchange of data between different fieldbus systems. Two modules form a communication pair that is installed in fieldbus nodes and connected by two twisted wire pairs. Data exchange is performed in full duplex operation, independent of the fieldbus system used. The data in the fieldbus couplers output process image is transmitted to the communication partner. This module then transmits the data to the input process image of its fieldbus coupler and vice versa. Factory preset transmission is 32 bits of input data and 32 bits of output data. Data transfer time for 32 bit-I/O is about 5 ms. The “function“ LED indicates a data exchange with the coupler. The status of the data transmission is indicated by the TxD and RxD LEDs.
Baud rate | 62.5 kBd |
Bit transfer | via 2 twisted pairs with differential signals |
Transmission channels | 1 TxD / 1 RxD, full-duplex |
Line length | approx. 1000 m twisted pair |
Data width | 1 x 32-bit input/output; 1 x 8-bit control/status |
Line impedance | 120 |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 65 |
Isolation | 500 V system/field |
Connection technology: inputs / outputs | 8 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 69.8 mm / 2.748 inches |
Depth from upper-edge of DIN-rail | 62.6 mm / 2.465 inches |
Mounting type | DIN-35 rail |
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.085 |
Weight | 49 |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-4, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |