Skip to main content
IIDM Logo
750-628

Description

The 750-628 Coupler Module for Internal Data Bus Extension replaces the fieldbus coupler/controller on a module assembly. It is also the mating piece for the 750-627 End Module. Plug the connection cable into the top RJ-45 socket to establish the logical link to the fieldbus coupler/controller via the 750-627 End Module. The extension is completely transparent for the fieldbus coupler/controller. All of the functions of the I/O module system are retained without any changes. A further extension to the system is provided by the bottom RJ-45 socket. This enables the entire system to be extended by 10 stages. The supply voltage for the field side and the internal electronics can be input separately. Both levels are electrically isolated from each other. Two diagnostic LEDs give information about the supply voltage for both the internal and field side. Two LEDs in the input socket indicate fault-free communication with the bus coupler. The module can be used as the last coupler module in the system (switch on matching resistor) or as a bridge between two I/O module assemblies.Installation note (NOTICE): In order to guarantee safe operating conditions when using the 750-627/-628 Coupler Modules for Internal Data Bus Extension, these must be registered prior to startup with the couplers or PLCs (refer to manual for supported couplers/PLCs). You must use the WAGO Extension Setting Software for this (Download: www.wago.com). Please note that only one terminating resistor may be activated in the whole system. Please complete the manufacturing number matrix on the right-hand side of the couplers when updating the firmware and internal operating parameters.

Technical data

Device-specific

Distance (max.): 5 m (10 m see manual); (end/coupler modules or coupler/coupler modules)

Transmission medium

Shielded copper cable (ETHERNET patch cable); 4 x 2 x 0.25 mm², twisted pair, double shielding, STP (Shielded Twisted-Pair)

Number of modules per node (max.)

64

Supply voltage (system)

24 VDC (-15 … +20 %); via pluggable connector (CAGE CLAMP® connection)

Current consumption (5 V system supply)

150

Total current (system supply)

400

Supply voltage (field)

24 VDC (-15 … +20 %); via power jumper contacts (power supply via CAGE CLAMP® connection; transmission via spring contact)

Input current (typ.) at nominal load (24 V)

200

Power supply efficiency (typ.) at nominal load (24 V)

76

Isolation

500 V system/field

Number of outgoing power jumper contacts

3

Current carrying capacity (power jumper contacts)

10

Connection data

Connection technology: communication/fieldbus

Local bus: 2 x RJ-45

Connection technology: field supply

6 x CAGE CLAMP®

Connection technology: system supply

2 x CAGE CLAMP®

Connection type 1

System/field supply

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Physical data

Width

24 mm / 0.945 inches

Height

100 mm / 3.937 inches

Depth

69.8 mm / 2.748 inches

Depth from upper-edge of DIN-rail

62.6 mm / 2.465 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

light gray

Housing material

Polycarbonate; polyamide 6.6

Fire load

0.016

Weight

74.8

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

0 … 2000 m / 0 … 6562 ft

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Vibration resistance

4g per IEC 60068-2-6

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61000-6-2, marine applications

EMC emission of interference

per EN 61000-6-4, marine applications

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Specifications

Connection data

Connectable Conductor MaterialsCopper
Connection Technology: Communication/FieldbusLocal bus: 2 x RJ-45
Connection Technology: Field Supply6 x CAGE CLAMP®
Connection Technology: System Supply2 x CAGE CLAMP®
Connection Type 1System/field supply
Fine-Stranded Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Solid Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Strip Length8 … 9 mm / 0.31 … 0.35 inches

Environmental requirements

Ambient Temperature (Operation)0 … +55 °C °C
EMC Emission Of Interferenceper EN 61000-6-4, marine applications
EMC Immunity To Interferenceper EN 61000-6-2, marine applications
Exposure To PollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Mounting Positionhorizontal (standing/lying); vertical
Operating Altitude0 … 2000 m / 0 … 6562 ft
Permissible Pollutant Concentration H2S At A Relative Humidity < 75%10
Permissible Pollutant Concentration SO 2 At A Relative Humidity < 75%25
Pollution Degree (5)2 per IEC 61131-2
Protection TypeIP20
Relative Humidity (Without Condensation)95
Shock Resistance15g per IEC 60068-2-27
Surrounding Air Temperature (Storage)-25 … +85 °C
Vibration Resistance4g per IEC 60068-2-6

Material data

Colorlight gray
Conformity MarkingCE
Fire Load0.016
Housing MaterialPolycarbonate; polyamide 6.6
Weight74.8

Mechanical data

Mounting TypeDIN-35 rail

Physical data

Depth69.8 mm / 2.748 inches mm
Depth From Upper-Edge Of DIN-Rail62.6 mm / 2.465 inches
Height100 mm / 3.937 inches mm
Width24 mm / 0.945 inches mm

Technical data

Current Carrying Capacity (Power Jumper Contacts)10
Current Consumption (5 V System Supply)150
Device-SpecificDistance (max.): 5 m (10 m see manual); (end/coupler modules or coupler/coupler modules)
Input Current (Typ.) At Nominal Load (24 V)200
Isolation500 V system/field
Number Of Modules Per Node (Max.)64
Number Of Outgoing Power Jumper Contacts3
Power Supply Efficiency (Typ.) At Nominal Load (24 V)76
Supply Voltage (Field)24 VDC (-15 … +20 %); via power jumper contacts (power supply via CAGE CLAMP® connection; transmission via spring contact)
Supply Voltage (System)24 VDC (-15 … +20 %); via pluggable connector (CAGE CLAMP® connection)
Total Current (System Supply)400
Transmission MediumShielded copper cable (ETHERNET patch cable); 4 x 2 x 0.25 mm², twisted pair, double shielding, STP (Shielded Twisted-Pair)