Skip to main content
IIDM Logo
750-307

Description

This fieldbus coupler connects the WAGO I/O System as a slave to the CANopen fieldbus. Data is transmitted via PDOs and SDOs. The fieldbus coupler detects all connected I/O modules and creates a local process image. Analog and specialty module data is sent via words and/or bytes, digital data is sent bit by bit. The local process image is divided into two data zones containing the data received and the data to be sent. The process data can be sent via the CANopen bus to a control system for further processing. The process output data is sent via the CANopen bus. The data of the analog modules is stored in the PDOs according to the order in which the modules are connected to the coupler. The bits from the digital modules are sent byte by byte and also mapped in the PDOs. If the amount of digital I/O information exceeds eight bits, the coupler automatically starts with a new byte. All entries of the object directory can be mapped as required in the five Rx PDOs and five Tx PDOs. The complete input and output process image can be transmitted using SDOs.

Notes

Note

For new installations, please consider the 750-337 Fieldbus Coupler with extended functionality.

Note: Configuration files required (EDS)!

Technical data

Communication

CANopen

Number of fieldbus nodes on master (max.)

110

Baud rate

10 kBd … 1 MBd

Bus segment length (max.)

1000 m

Transmission medium

Shielded Cu cable 3 x 0.25 mm²

Number of modules per node (max.)

64

Other CANopen features

NMT slave

Minimum boot-up

Variable PDO mapping

Emergency message

Life guarding

Number of PDOs

5 Tx / 5 Rx

Number of SDOs

2 SDO servers

COB ID distribution

SDO, standard

Node ID distribution

DIP switch

Communication profile

DS-301 V3.0

Device profile

DS-401 V1.4

Input and output process image (fieldbus) max.

512 bytes/512 bytes

Supply voltage (system)

24 VDC (-15 … +20 %); via pluggable connector (CAGE CLAMP® connection)

Current consumption (5 V system supply)

350

Total current (system supply)

1,650

Supply voltage (field)

24 VDC (-15 … +20 %); via power jumper contacts

Input current (typ.) at nominal load (24 V)

500

Power supply efficiency (typ.) at nominal load (24 V)

87

Isolation

500 V system/field

Number of outgoing power jumper contacts

3

Current carrying capacity (power jumper contacts)

10

Connection data

Connection technology: communication/fieldbus

CANopen: 1 x Male connector; 5-pole

Connection technology: field supply

6 x CAGE CLAMP®

Connection technology: system supply

2 x CAGE CLAMP®

Connection technology: device configuration

1 x Male connector; 4-pole

Connection type 1

System/field supply

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Physical data

Width

50.5 mm / 1.988 inches

Height

100 mm / 3.937 inches

Depth

71.1 mm / 2.799 inches

Depth from upper-edge of DIN-rail

63.9 mm / 2.516 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

light gray

Housing material

Polycarbonate; polyamide 6.6

Fire load

5.156

Weight

200

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

0 … 2000 m / 0 … 6562 ft

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Vibration resistance

per IEC 60068-2-6

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61000-6-2

EMC emission of interference

per EN 61000-6-4

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Specifications

Connection data

Connection Technology: Communication/FieldbusCANopen: 1 x Male connector; 5-pole
Connection Technology: Device Configuration1 x Male connector; 4-pole
Connection Technology: Field Supply6 x CAGE CLAMP®
Connection Technology: System Supply2 x CAGE CLAMP®
Connection Type 1System/field supply
Fine-Stranded Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Solid Conductor0.08 … 2.5 mm² / 28 … 14 AWG
Strip Length8 … 9 mm / 0.31 … 0.35 inches

Environmental requirements

Ambient Temperature (Operation)0 … +55 °C °C
EMC Emission Of Interferenceper EN 61000-6-4
EMC Immunity To Interferenceper EN 61000-6-2
Exposure To PollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Mounting Positionhorizontal (standing/lying); vertical
Operating Altitude0 … 2000 m / 0 … 6562 ft
Permissible Pollutant Concentration H2S At A Relative Humidity < 75%10
Permissible Pollutant Concentration SO 2 At A Relative Humidity < 75%25
Pollution Degree (5)2 per IEC 61131-2
Protection TypeIP20
Relative Humidity (Without Condensation)95
Shock Resistance15g per IEC 60068-2-27
Surrounding Air Temperature (Storage)-25 … +85 °C
Vibration Resistanceper IEC 60068-2-6

Material data

Colorlight gray
Conformity MarkingCE
Fire Load5.156
Housing MaterialPolycarbonate; polyamide 6.6
Weight200

Mechanical data

Mounting TypeDIN-35 rail

Notes

NoteFor new installations, please consider the 750-337 Fieldbus Coupler with extended functionality.Note: Configuration files required (EDS)!

Physical data

Depth71.1 mm / 2.799 inches mm
Depth From Upper-Edge Of DIN-Rail63.9 mm / 2.516 inches
Height100 mm / 3.937 inches mm
Width50.5 mm / 1.988 inches mm

Technical data

Baud Rate10 kBd … 1 MBd
Bus Segment Length (Max.)1000 m
COB ID DistributionSDO, standard
CommunicationCANopen
Communication ProfileDS-301 V3.0
Current Carrying Capacity (Power Jumper Contacts)10
Current Consumption (5 V System Supply)350
Device ProfileDS-401 V1.4
Input And Output Process Image (Fieldbus) Max.512 bytes/512 bytes
Input Current (Typ.) At Nominal Load (24 V)500
Isolation500 V system/field
Node ID DistributionDIP switch
Number Of Fieldbus Nodes On Master (Max.)110
Number Of Modules Per Node (Max.)64
Number Of Outgoing Power Jumper Contacts3
Number Of PDOs5 Tx / 5 Rx
Number Of SDOs2 SDO servers
Other CANopen FeaturesNMT slave | Minimum boot-up | Variable PDO mapping | Emergency message | Life guarding
Power Supply Efficiency (Typ.) At Nominal Load (24 V)87
Supply Voltage (Field)24 VDC (-15 … +20 %); via power jumper contacts
Supply Voltage (System)24 VDC (-15 … +20 %); via pluggable connector (CAGE CLAMP® connection)
Total Current (System Supply)1,650
Transmission MediumShielded Cu cable 3 x 0.25 mm²

Similar products

More from Wago