Wago
Part No. 750-331

This fieldbus coupler connects the WAGO I/O System as a slave to the CANopen fieldbus. Data is transmitted via PDOs and SDOs. The fieldbus coupler detects all connected I/O modules and creates a local process image. Analog and specialty module data is sent via words and/or bytes, digital data is sent bit by bit. The local process image is divided into two data zones containing the data received and the data to be sent. The process data can be sent via the CANopen bus to a control system for further processing. The process output data is sent via the CANopen bus. The data of the analog modules is stored in the PDOs according to the order in which the modules are connected to the coupler. The bits from the digital modules are sent byte by byte and also mapped in the PDOs. If the amount of digital I/O information exceeds eight bits, the coupler automatically starts with a new byte. All entries of the object directory can be mapped as required in the five Rx PDOs and five Tx PDOs. The complete input and output process image can be transmitted using SDOs.
Note | For new installations, please consider the 750-337 Fieldbus Coupler with extended functionality. Note: Configuration files required (EDS)! |
Communication | CANopen |
Number of fieldbus nodes on master (max.) | 110 |
Baud rate | 10 kBd … 1 MBd |
Bus segment length (max.) | 1000 m |
Transmission medium | Shielded Cu cable 3 x 0.25 mm² |
Number of modules per node (max.) | 64 |
Other CANopen features | NMT slave Minimum boot-up Variable PDO mapping Emergency message Life guarding |
Number of PDOs | 5 Tx / 5 Rx |
Number of SDOs | 2 SDO servers |
COB ID distribution | SDO, standard |
Node ID distribution | DIP switch |
Communication profile | DS-301 V3.0 |
Device profile | DS-401 V1.4 |
Input and output process image (fieldbus) max. | 512 bytes/512 bytes |
Supply voltage (system) | 24 VDC (-15 … +20 %); via pluggable connector (CAGE CLAMP® connection) |
Current consumption (5 V system supply) | 350 |
Total current (system supply) | 1,650 |
Supply voltage (field) | 24 VDC (-15 … +20 %); via power jumper contacts |
Input current (typ.) at nominal load (24 V) | 500 |
Power supply efficiency (typ.) at nominal load (24 V) | 87 |
Isolation | 500 V system/field |
Number of outgoing power jumper contacts | 3 |
Current carrying capacity (power jumper contacts) | 10 |
Connection technology: communication/fieldbus | CANopen: 1 x Male connector; 5-pole |
Connection technology: field supply | 6 x CAGE CLAMP® |
Connection technology: system supply | 2 x CAGE CLAMP® |
Connection technology: device configuration | 1 x Male connector; 4-pole |
Connection type 1 | System/field supply |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Width | 50.5 mm / 1.988 inches |
Height | 100 mm / 3.937 inches |
Depth | 71.1 mm / 2.799 inches |
Depth from upper-edge of DIN-rail | 63.9 mm / 2.516 inches |
Mounting type | DIN-35 rail |
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 5.156 |
Weight | 200 |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2 |
EMC emission of interference | per EN 61000-6-4 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |