Skip to main content
IIDM Logo
103014754

Description

Productfeatures
  • 2 Safety contacts, 1 Safety Output
  • Plug-in screw terminals with coding
  • 1 Signalling output - status safety module
  • 1 Signalling output - failure massage dynamic
  • Detects standstill using 1 or 2 impulse sensors
  • additional standstill signal, e.g. PLC as second input channel
  • 2-channel time monitoring
Data
Ordering data

Product type description

SRB-E-302FWS-TS

Article number (order number)

103014754

EAN (European Article Number)

4030661511276

eCl@ss number, version 9.0

27-37-18-19

eCl@ss number, version 11.0

27-37-18-19

eCl@ss number, version 12.0

27-37-18-19

ETIM number, version 7.0

EC001449

ETIM number, version 6.0

EC001449

Approvals - Standards

Certificates

TÜV

cULus

CCC

General data

Standards

EN 60204-1

EN 60947-5-1

EN 60947-5-5

EN ISO 13849-1

IEC 61508

Climatic stress

EN 60068-2-78

Enclosure material

Glass-fibre reinforced thermoplastic, ventilated

Material of the contacts, electrical

Ag-Ni, self-cleaning, positive drive

Gross weight

170 g

General data - Features

Stop-Category

0

Electronic Fuse

Yes

Wire breakage detection

Yes

Cross-circuit detection

Yes

Start input

Yes

Feedback circuit

Yes

Automatic reset function

Yes

Reset edge detection

Yes

Earth connection detection

Yes

Integral system diagnostics, status

Yes

Number of inputs for NC

2

Number of inputs for NO

1

Number of LEDs

6

Number of safety contacts

2

Number of fail-safe digital outputs

1

Number of signalling outputs

2

Mechanical data

Mechanical life, minimum

10,000,000 Operations

Mounting

Snaps onto standard DIN rail to EN 60715

Mechanical data - Connection technique

Type of connection

Screw connection, plug-in

rigid or flexible

Terminal designations

IEC 60947-1

Cable section, minimum

0.25 mm²

Cable section, maximum

2.5 mm²

Tightening torque of Clips

0.5 Nm

Mechanical data - Dimensions

Width

22.5 mm

Height

98 mm

Depth

115 mm

Ambient conditions

Degree of protection of the enclosure

IP40

Degree of protection of the mounting space

IP54

Degree of protection of clips or terminals

IP20

Ambient temperature, minimum

-25 °C

Ambient temperature, maximum

+60 °C

Storage and transport temperature, minimum

-40 °C

Storage and transport temperature, maximum

+85 °C

Resistance to vibration to EN 60068-2-6

10 ... 55 Hz, Amplitude 0.35 mm

Restistance to shock

30 g / 11 ms

Ambient conditions - Insulation values

Rated insulation voltage U

250 V / 50 V

Rated impulse withstand voltage, relay output U

4 kV

Rated impulse withstand voltage, semiconductor output U

0.8 kV

Overvoltage category

III

Degree of pollution to IEC/EN 60664-1

2

Electrical data

Rated operating voltage

24 VDC -20%/+20%, residual ripple max. 10%

Operating current

125 mA

Rated AC voltage for controls at DC minimum

19.2 VDC

Rated control voltage at DC, maximum

28.8 VDC

Electrical power consumption

3 W

Contact resistance, maximum

0.1 Ω

Note (Contact resistance)

in new state

Drop-out delay in case of power failure, typically

10 ms

Drop-out delay in case of emergency, typically

10 ms

Pull-in delay at automatic start, maximum, typically

150 ms

ON delay at automatic start

Adjustable

Pull-in delay at RESET, typically

150 ms

Switching frequency, maximum

0.3 Hz

Electrical data - Safety digital outputs

Voltage drop U

0.5 V

Leakage current I

1 mA

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

2 A

Electrical data - Safe relay outputs

Voltage, Utilisation category AC-15

230 VAC

Current, Utilisation category AC-15

4 A

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

4 A

Switching capacity, minimum

10 VDC

Switching capacity, minimum

10 mA

Switching capacity, maximum

250 VAC

Switching capacity, maximum

6 A

Electrical data - Digital inputs

Conduction resistance, maximum

40 Ω

Electrical data - Digital Output

Voltage, Utilisation category DC-12

24 VDC

Current, Utilisation category DC-12

0.1 A

Electrical data - Relay outputs (auxiliary contacts)

Switching capacity, maximum

24 VDC

Switching capacity, maximum

1 A

Specifications

Data › Ambient conditions

Ambient Temperature, Maximum+60 °C
Ambient Temperature, Minimum-25 °C
Degree Of Protection Of Clips Or TerminalsIP20
Degree Of Protection Of The EnclosureIP40
Degree Of Protection Of The Mounting SpaceIP54
Resistance To Vibration To EN 60068-2-610 ... 55 Hz, Amplitude 0.35 mm
Restistance To Shock30 g / 11 ms
Storage And Transport Temperature, Maximum+85 °C
Storage And Transport Temperature, Minimum-40 °C

Data › Ambient conditions - Insulation values

Degree Of Pollution To IEC/EN 60664-12
Overvoltage CategoryIII
Rated Impulse Withstand Voltage, Relay Output U4 kV
Rated Impulse Withstand Voltage, Semiconductor Output U0.8 kV
Rated Insulation Voltage U250 V / 50 V

Data › Approvals - Standards

CertificatesTÜV | cULus | CCC

Data › Electrical data

Contact Resistance, Maximum0.1 Ω
Drop-Out Delay In Case Of Emergency, Typically10 ms
Drop-Out Delay In Case Of Power Failure, Typically10 ms
Electrical Power Consumption3 W
Note (Contact Resistance)in new state
ON Delay At Automatic StartAdjustable
Operating Current125 mA
Pull-In Delay At Automatic Start, Maximum, Typically150 ms
Pull-In Delay At RESET, Typically150 ms
Rated AC Voltage For Controls At DC Minimum19.2 VDC
Rated Control Voltage At DC, Maximum28.8 VDC
Rated Operating Voltage24 VDC -20%/+20%, residual ripple max. 10%
Switching Frequency, Maximum0.3 Hz

Data › Electrical data - Digital inputs

Conduction Resistance, Maximum40 Ω

Data › Electrical data - Digital Output

Current, Utilisation Category DC-120.1 A
Voltage, Utilisation Category DC-1224 VDC

Data › Electrical data - Safe relay outputs

Current, Utilisation Category AC-154 A
Switching Capacity, Maximum250 VAC | 6 A | 24 VDC | 1 A
Switching Capacity, Minimum10 VDC | 10 mA
Voltage, Utilisation Category AC-15230 VAC

Data › Electrical data - Safety digital outputs

Current, Utilisation Category DC-132 A | 4 A
Leakage Current I1 mA
Voltage Drop U0.5 V
Voltage, Utilisation Category DC-1324 VDC

Data › General data

Climatic StressEN 60068-2-78
Enclosure MaterialGlass-fibre reinforced thermoplastic, ventilated
Gross Weight170 g
Material Of The Contacts, ElectricalAg-Ni, self-cleaning, positive drive
StandardsEN 60204-1 | EN 60947-5-1 | EN 60947-5-5 | EN ISO 13849-1 | IEC 61508

Data › General data - Features

Automatic Reset FunctionYes
Cross-Circuit DetectionYes
Earth Connection DetectionYes
Electronic FuseYes
Feedback CircuitYes
Integral System Diagnostics, StatusYes
Number Of Fail-Safe Digital Outputs1
Number Of Inputs For NC2
Number Of Inputs For NO1
Number Of LEDs6
Number Of Safety Contacts2
Number Of Signalling Outputs2
Reset Edge DetectionYes
Start InputYes
Stop-Category0
Wire Breakage DetectionYes

Data › Mechanical data

Mechanical Life, Minimum10,000,000 Operations
MountingSnaps onto standard DIN rail to EN 60715

Data › Mechanical data - Connection technique

Cable Section, Maximum2.5 mm²
Cable Section, Minimum0.25 mm²
Terminal DesignationsIEC 60947-1
Tightening Torque Of Clips0.5 Nm
Type Of ConnectionScrew connection, plug-in | rigid or flexible

Data › Mechanical data - Dimensions

Depth115 mm mm
Height98 mm mm
Width22.5 mm mm

Data › Ordering data

Article Number (Order Number)103014754
EAN (European Article Number)4030661511276
ECl@Ss Number, Version 11.027-37-18-19
ECl@Ss Number, Version 12.027-37-18-19
ECl@Ss Number, Version 9.027-37-18-19
ETIM Number, Version 6.0EC001449
ETIM Number, Version 7.0EC001449
Product Type DescriptionSRB-E-302FWS-TS