Skip to main content
IIDM Logo
103008067103008067103008067

Description

Productfeatures
  • Plug-in screw terminals with coding
  • STOP 0 Function
  • 1 oder 2-channel control
  • Start button / Auto-start
  • Monitoring two-hand control panels to EN 574 IIIC
  • 2 Safety outputs 5.5 A
  • 1 Signalling output
Data
Ordering data

Product type description

SRB-E-201ST

Article number (order number)

103008067

EAN (European Article Number)

4030661478456

eCl@ss number, version 9.0

27-37-18-19

eCl@ss number, version 11.0

27-37-18-19

eCl@ss number, version 12.0

27-37-18-19

ETIM number, version 7.0

EC001449

ETIM number, version 6.0

EC001449

Approvals - Standards

Certificates

TÜV

cULus

CCC

EAC

General data

Standards

EN 60204-1

EN 60947-5-1

EN ISO 13849-1

IEC 61508

IEC 62061

Climatic stress

EN 60068-2-78

Enclosure material

Glass-fibre reinforced thermoplastic, ventilated

Gross weight

130 g

General data - Features

Stop-Category

0

Electronic Fuse

Yes

Wire breakage detection

Yes

Cross-circuit detection

Yes

Removable Terminals

Yes

Start input

Yes

Feedback circuit

Yes

Automatic reset function

Yes

Reset edge detection

Yes

Earth connection detection

Yes

Integral system diagnostics, status

Yes

Integral system diagnostics, error code

Yes

Number of LEDs

5

Number of openers

2

Number of shutters

1

Number of fail-safe outputs, Stop 0

2

Number of signalling outputs

1

Mechanical data

Mounting

Snaps onto standard DIN rail to EN 60715

Mechanical data - Connection technique

Type of connection

Screw connection, plug-in

rigid or flexible

Terminal designations

IEC/EN 60947-1

Cable section, minimum

0.25 mm²

Cable section, maximum

2.5 mm²

Tightening torque of Clips

0.5 Nm

Mechanical data - Dimensions

Width

22.5 mm

Height

98 mm

Depth

115 mm

Ambient conditions

Degree of protection of the enclosure

IP40

Degree of protection of the mounting space

IP54

Degree of protection of clips or terminals

IP20

Ambient temperature, minimum

-25 °C

Ambient temperature, maximum

+60 °C

Storage and transport temperature, minimum

-40 °C

Storage and transport temperature, maximum

+85 °C

Resistance to vibration to EN 60068-2-6

10 ... 55 Hz, Amplitude 0.35 mm

Restistance to shock

30 g / 11 ms

Ambient conditions - Insulation values

Rated impulse withstand voltage U

0.8 kV

Overvoltage category

III

Degree of pollution to IEC/EN 60664-1

2

Electrical data

Rated operating voltage

24 VDC -20%/+20%, residual ripple max. 10%

Operating current

100 mA

Rated AC voltage for controls at DC minimum

19.2 VDC

Rated control voltage at DC, maximum

28.8 VDC

Electrical power consumption

2.4 W

Drop-out delay in case of power failure, typically

10 ms

Drop-out delay in case of emergency, typically

10 ms

Pull-in delay at automatic start, maximum, typically

150 ms

Pull-in delay at RESET, typically

150 ms

Switching frequency, maximum

1 Hz

Electrical data - Safety digital outputs

Voltage drop U

0.5 V

Leakage current I

1 mA

Voltage, Utilisation category DC-12

24 VDC

Current, Utilisation category DC-12

5.5 A

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

3.5 A

Electrical data - Digital inputs

Conduction resistance, maximum

40 Ω

Electrical data - Digital Output

Voltage, Utilisation category DC-12

24 VDC

Current, Utilisation category DC-12

0.1 A

Electrical data - Electromagnetic compatibility (EMC)

EMC rating

EMC-Directive

Specifications

Data › Ambient conditions

Ambient Temperature, Maximum+60 °C
Ambient Temperature, Minimum-25 °C
Degree Of Protection Of Clips Or TerminalsIP20
Degree Of Protection Of The EnclosureIP40
Degree Of Protection Of The Mounting SpaceIP54
Resistance To Vibration To EN 60068-2-610 ... 55 Hz, Amplitude 0.35 mm
Restistance To Shock30 g / 11 ms
Storage And Transport Temperature, Maximum+85 °C
Storage And Transport Temperature, Minimum-40 °C

Data › Ambient conditions - Insulation values

Degree Of Pollution To IEC/EN 60664-12
Overvoltage CategoryIII
Rated Impulse Withstand Voltage U0.8 kV

Data › Approvals - Standards

CertificatesTÜV | cULus | CCC | EAC

Data › Electrical data

Drop-Out Delay In Case Of Emergency, Typically10 ms
Drop-Out Delay In Case Of Power Failure, Typically10 ms
Electrical Power Consumption2.4 W
Operating Current100 mA
Pull-In Delay At Automatic Start, Maximum, Typically150 ms
Pull-In Delay At RESET, Typically150 ms
Rated AC Voltage For Controls At DC Minimum19.2 VDC
Rated Control Voltage At DC, Maximum28.8 VDC
Rated Operating Voltage24 VDC -20%/+20%, residual ripple max. 10%
Switching Frequency, Maximum1 Hz

Data › Electrical data - Digital inputs

Conduction Resistance, Maximum40 Ω

Data › Electrical data - Electromagnetic compatibility (EMC)

EMC RatingEMC-Directive

Data › Electrical data - Safety digital outputs

Current, Utilisation Category DC-125.5 A | 0.1 A
Current, Utilisation Category DC-133.5 A
Leakage Current I1 mA
Voltage Drop U0.5 V
Voltage, Utilisation Category DC-1224 VDC
Voltage, Utilisation Category DC-1324 VDC

Data › General data

Climatic StressEN 60068-2-78
Enclosure MaterialGlass-fibre reinforced thermoplastic, ventilated
Gross Weight130 g
StandardsEN 60204-1 | EN 60947-5-1 | EN ISO 13849-1 | IEC 61508 | IEC 62061

Data › General data - Features

Automatic Reset FunctionYes
Cross-Circuit DetectionYes
Earth Connection DetectionYes
Electronic FuseYes
Feedback CircuitYes
Integral System Diagnostics, Error CodeYes
Integral System Diagnostics, StatusYes
Number Of Fail-Safe Outputs, Stop 02
Number Of LEDs5
Number Of Openers2
Number Of Shutters1
Number Of Signalling Outputs1
Removable TerminalsYes
Reset Edge DetectionYes
Start InputYes
Stop-Category0
Wire Breakage DetectionYes

Data › Mechanical data

MountingSnaps onto standard DIN rail to EN 60715

Data › Mechanical data - Connection technique

Cable Section, Maximum2.5 mm²
Cable Section, Minimum0.25 mm²
Terminal DesignationsIEC/EN 60947-1
Tightening Torque Of Clips0.5 Nm
Type Of ConnectionScrew connection, plug-in | rigid or flexible

Data › Mechanical data - Dimensions

Depth115 mm mm
Height98 mm mm
Width22.5 mm mm

Data › Ordering data

Article Number (Order Number)103008067
EAN (European Article Number)4030661478456
ECl@Ss Number, Version 11.027-37-18-19
ECl@Ss Number, Version 12.027-37-18-19
ECl@Ss Number, Version 9.027-37-18-19
ETIM Number, Version 6.0EC001449
ETIM Number, Version 7.0EC001449
Product Type DescriptionSRB-E-201ST