Skip to main content
IIDM Logo
101019461

Description

Productfeatures
  • without Locking sleeve
  • 8 Contacts
  • Mounting depth 91 mm
  • 4 switch position
  • Mounting hole 30.5 mm
  • Mounting mounting flange
  • up to 10 mm front plate thickness
Data
Ordering data

Product type description

WKTE52

Article number (order number)

101019461

eCl@ss number, version 9.0

27-37-14-04

eCl@ss number, version 11.0

27-37-14-04

eCl@ss number, version 12.0

27-37-14-04

ETIM number, version 7.0

EC000632

ETIM number, version 6.0

EC000632

Approvals - Standards

Certificates

cURus

General data

Standards

IEC/EN 60947-1

IEC/EN 60947-5-1

Climatic stress

IEC/EN 60068-2-20

Installation conditions (mechanical)

arbitrarily

Material of the front ring

Aluminium - anodised

Material of the bellows

Rubber

Material thickness of the sealing bellows

1 mm

Colour of the front ring

Silver

Colour of the bellows

Black

Gross weight

230 g

General data - Features

Return to zero position

Yes

External applications

Yes

Galvanically separated contact bridges

Yes

Probing possible

Yes

Number of auxiliary contacts

8

Number of directions

4

Number of shutters per direction

2

Number of switch positions

4

Number of switching stages

4

Mechanical data

Latching position

right

left

bottom

above

Mechanical life, minimum

1,000,000 Operations

Actuating force, approx.

11 N

Mounting

mounting flange

Mechanical data - Connection technique

Type of connection

Screw terminals M20 x 1.5

Cable section, minimum

0.5 mm²

Cable section, maximum

2.5 mm²

Note (Cable section)

All indications including the conductor ferrules.

Mechanical data - Dimensions

Mounting depth

91 mm

Length of the actuator

90 mm

Diameter hole

30.5 mm

Diameter hole, central mounting

31 mm

Thickness, of the front panel, minimum

1.5 mm

Thickness of the front panel, maximum

10 mm

Diameter for the Installation to IEC/EN 60947-1

30.5 + 0.5 mm

Spacing

80 x 80 mm

Ambient conditions

Degree of protection

IP65

IP67

Ambient temperature, minimum

-25 °C

Ambient temperature, maximum

+80 °C

Resistance to vibration to EN 60068-2-6

10 … 200 Hz, with 20 g

Restistance to shock

110 g / 4 ms - 30 g / 18 ms

Ambient conditions - Insulation values

Rated insulation voltage U

400 V

Rated impulse withstand voltage U

4 kV

Degree of pollution to IEC/EN 60947-1

3

Electrical data

Thermal test current

10 A

Utilisation category AC-15

250 VAC

Utilisation category AC-15

8 A

Utilisation category DC-13

24 VDC

Utilisation category DC-13

5 A

Switching element

2 NO contacts / 2 NO contacts / 2 NO contacts / 2 NO contacts

Switching principle

Creep circuit element

Switching frequency

1,200 /h

Note

Notice (switch position)

Position A, B, C, D

Specifications

Data › Ambient conditions

Ambient Temperature, Maximum+80 °C
Ambient Temperature, Minimum-25 °C
Degree Of ProtectionIP65 | IP67
Resistance To Vibration To EN 60068-2-610 … 200 Hz, with 20 g
Restistance To Shock110 g / 4 ms - 30 g / 18 ms

Data › Ambient conditions - Insulation values

Degree Of Pollution To IEC/EN 60947-13
Rated Impulse Withstand Voltage U4 kV
Rated Insulation Voltage U400 V

Data › Approvals - Standards

CertificatescURus

Data › Electrical data

Switching Element2 NO contacts / 2 NO contacts / 2 NO contacts / 2 NO contacts
Switching Frequency1,200 /h
Switching PrincipleCreep circuit element
Thermal Test Current10 A
Utilisation Category AC-15250 VAC | 8 A
Utilisation Category DC-1324 VDC | 5 A

Data › General data

Climatic StressIEC/EN 60068-2-20
Colour Of The BellowsBlack
Colour Of The Front RingSilver
Gross Weight230 g
Installation Conditions (Mechanical)arbitrarily
Material Of The BellowsRubber
Material Of The Front RingAluminium - anodised
Material Thickness Of The Sealing Bellows1 mm
StandardsIEC/EN 60947-1 | IEC/EN 60947-5-1

Data › General data - Features

External ApplicationsYes
Galvanically Separated Contact BridgesYes
Number Of Auxiliary Contacts8
Number Of Directions4
Number Of Shutters Per Direction2
Number Of Switching Stages4
Number Of Switch Positions4
Probing PossibleYes
Return To Zero PositionYes

Data › Mechanical data

Actuating Force, Approx.11 N
Latching Positionright | left | bottom | above
Mechanical Life, Minimum1,000,000 Operations
Mountingmounting flange

Data › Mechanical data - Connection technique

Cable Section, Maximum2.5 mm²
Cable Section, Minimum0.5 mm²
Note (Cable Section)All indications including the conductor ferrules.
Type Of ConnectionScrew terminals M20 x 1.5

Data › Mechanical data - Dimensions

Diameter For The Installation To IEC/EN 60947-130.5 + 0.5 mm
Diameter Hole30.5 mm
Diameter Hole, Central Mounting31 mm
Length Of The Actuator90 mm
Mounting Depth91 mm
Spacing80 x 80 mm
Thickness Of The Front Panel, Maximum10 mm
Thickness, Of The Front Panel, Minimum1.5 mm

Data › Note

Notice (Switch Position)Position A, B, C, D

Data › Ordering data

Article Number (Order Number)101019461
ECl@Ss Number, Version 11.027-37-14-04
ECl@Ss Number, Version 12.027-37-14-04
ECl@Ss Number, Version 9.027-37-14-04
ETIM Number, Version 6.0EC000632
ETIM Number, Version 7.0EC000632
Product Type DescriptionWKTE52

Similar products